| Conductor |
| Material | Oxygen free copper (≥99.97% purity) |
| Diameter | 0.50 mm ± 0.01 mm |
| American Wire Gauge (AWG) | 24AWG |
| Insulation |
| Material | HDPE |
| Min. Average Thickness | 0.18 mm |
| Diameter | 0.90 mm ± 0.05 mm |
| Color (4 Pairs) | Blue, white/blue; orange, white/orange; green, white/green; brown, white/brown |
| Rip Cord |
| Material | Polyester |
| Specification | 500D |
| Sheath |
| Material | PVC |
| Min. Average Thickness | 0.5 mm |
| Diameter | 5.1 mm ± 0.2 mm |
| Color | White |
| Electrical |
| Max. DC Resistance of a Single Conductor | 9.5 Ω/100 m |
| Min. Insulation Resistance | 5000 MΩ·km |
| Max. DC Resistance Unbalance | 5% (pair intra) |
| Dielectric Strength | No breakdown with 2.5 KV DC for 2 seconds |
| Transmission |
| Characteristic Impedance | 100 ± 15 Ω |
| Near End Cross Talk (NEXT) | ≥35.30 dB/100 m @100 MHz |
| Max. Attenuation | 22.0 dB/100 m @100 MHz |
| Return Loss | ≥20.1 dB/100 m @100 MHz |
| Mechanical |
| Tensile Strength | Sheath ≥13.8 MPa, insulation ≥16.5 MPa |
| Elongation at Break | Sheath ≥100%, insulation ≥300% |
| Installation Bending Radius | >8 times of outer cable diameter |
| Conductor Elongation at Break | ≥10% |
| Environmental |
| Shrinkage of Insulation | ≤6% |
| Color Migration Resistance of Insulation | No migration |
| Sheath Tensile Strength and Elongation at Break after Aging | ≥11.73 MPa, ≥50% |
| Low Temperature Bending Test | No cracking after the test |
| Heat Shock Test | No cracking after the test |
| Operating Temperature | –20°C to +60°C (–4°F to 140°F) |
| Installation Temperature | 0°C to +50°C (32°F to 122°F) |
| Storage Temperature and Humidity | –10°C to +40°C (14°F to 104°F), <60% (RH) |
| Security |
| Vertical Fire Propagation Test | Comply with IEC 60332-1-2 |
| Packaging |
| Cable Length | 305.0 m (1000.66 ft) ± 1.5 m (4.92 ft) |
| Inner Carton Dimensions | 364.0 mm × 364.0 mm × 216.0 mm (14.33" × 14.33" × 8.50") (L × W × H) |
| Packaging Method | 305.0 m (1000.66 ft) a carton, one carton with 2 inner cartons |
| Net Weight | ≥8.0 kg (17.64 lb) |
| Gross Weight | ≥9.0 kg (19.84 lb) |
| Compliance |
| Executive Standards | ISO/IEC 11801-1-2017, IEC 61156-5-2009 |
| Certification |
| Certification | CPR Eca |
| Transmission Characteristics (100 m at 20°C) (328.08 ft at 68°F) |
| Frequency (MHz) | Phase delay ≤ ns | IL ≤ dB | NEXT ≥ dB | PS NEXT ≥ dB | ACRF ≥ dB |
| 1 | 570 | 2.0 | 65.3 | 62.3 | 63.8 |
| 4 | 552 | 4.1 | 56.3 | 53.3 | 51.8 |
| 8 | 547 | 5.8 | 51.8 | 48.8 | 45.7 |
| 10 | 545 | 6.5 | 50.3 | 47.3 | 43.8 |
| 16 | 543 | 8.2 | 47.2 | 44.2 | 39.7 |
| 20 | 542 | 9.3 | 45.8 | 42.8 | 37.8 |
| 25 | 541 | 10.4 | 44.3 | 41.3 | 35.8 |
| 31.25 | 540 | 11.7 | 42.9 | 39.9 | 33.9 |
| 62.5 | 539 | 17.0 | 38.4 | 35.4 | 27.9 |
| 100 | 538 | 22.0 | 35.3 | 32.3 | 23.8 |
| Frequency (MHz) | PS ACRF ≥ dB | RL ≥ dB | Delay skew ≤ ns | Zc (Ω) |
| 1 | n/s | n/s | n/s | n/s |
| 4 | 60.8 | 23.0 | 45.0 | 100±15 |
| 8 | 42.7 | 24.5 | 45.0 | 100±15 |
| 10 | 40.8 | 25.0 | 45.0 | 100±15 |
| 16 | 36.7 | 25.0 | 45.0 | 100±15 |
| 20 | 34.8 | 25.0 | 45.0 | 100±15 |
| 25 | 32.8 | 24.3 | 45.0 | 100±15 |
| 31.25 | 30.9 | 23.6 | 45.0 | 100±15 |
| 62.5 | 24.9 | 21.5 | 45.0 | 100±15 |
| 100 | 20.8 | 20.1 | 45.0 | 100±15 |
|
| Note: Executive standard for the above parameters: ANSI/TIA-568-C.2-2009 |