Stock Code: HY-C132

| Technical Specification | |
|---|---|
| Working Voltage | DC9V-DC30V |
| Rated Power | 3.408mW |
| Current | Standby current: ≤ 45µA Alarm current: ≤ 24mA |
| Sensor Class | A2R |
| Fixed Detection Threshold | 62°C ± 3°C (144°F ± 37.4°F) |
| Dynamic Detection | 1 to 30 K min⁻¹ |
| Alarm Mode | Visual alarm |
| Coverage Area | H ≤ 4 m (13.12 ft): 50 m² 4 m (13.12 ft) ≤ H ≤ 12 m (39.37 ft): 30 m² |
| Operating Temperature | –10°C to +50°C (+14°F to +122°F) |
| Operating Humidity | ≤ 95% RH (no condensation) |
| Dimensions (with base) | Φ100 mm × 50 mm (Φ 3.00" × 2.13") |
| Weight (with base) | 81 g (0.18 lb) |
| Installation | Ceiling Mount |
| Compliance Standard | EN 54-5 |