Stock Code: HY-1410C
| Electrical | |
|---|---|
| Working Voltage | 24V DC |
| Current | Monitoring current: ≤ 150 µA Operating current: ≤ 8 mA |
| Capacity of the Output Contact | 30V DC@1A |
| Indicator | Input indicator: Red LED flashes once every 6 seconds, flashes once every 2 seconds when malfunctioned, and stays on after feedback is received Output indicator: Red LED is off in normal state, flashes once every 2 seconds when malfunctioned, and stays on after the activation signal is received |
| Communication | |
| Wiring | Two-wire, polarity-free |
| Addressing Method | Electrical encoder |
| Address Range | 1–254 |
| Communication Distance | ≤ 1500 m |
| Environment | |
| Operating Temperature | –10°C to +55°C (+14°F to +131°F) |
| Storage Temperature | –20°C to +65°C (–4°F to +149°F) |
| Operating Humidity | ≤ 95% RH (no condensation) |
| Construction | |
| Color | White |
| Dimensions (with base) | 90 mm × 90 mm × 37 mm (3.54" × 3.54" × 1.46") |
| Weight (with base) | 117 g (0.26 lb) |
| Certification | GB16806-2006 |