Stock Code: DRL-48V240W1EN
| Output | |
|---|---|
| Output Current | 5 A |
| Output Voltage | 48 V |
| Output Voltage Range | 43.2-52.8 Vdc |
| Output Voltage Adjustment Range | 43.2-52.8 Vdc |
| Output Power | 240 W |
| Line Regulation | ± 0.5% @ 115 Vac & 230 Vac |
| Load Regulation | ± 0.5% |
| PARD (20 MHz) | < 200 mVpp @ 0°C to +70°C < 600 mVpp @ -30°C to 0°C |
| Start-up Time | 500 ms typ. @ 115 Vac & 230 Vac |
| Hold-up Time | 20 ms typ. @ 115 Vac (100% load) 20 ms typ. @ 230 Vac (100% load) |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 10% @ 115 Vac & 230 Vac input, 10-100% load (Slew Rate: 2.5 A/µS, 50% duty cycle @ 5 Hz & 10 kHz) |
| Start-up with Capacitive Loads | 3,000 µF Max |
| Rise Time | 30 ms typ. @ 115 Vac & 230 Vac |
| Input | |
| Nominal Input Voltage | 100-240 Vac |
| Input Voltage Range | 90-264 Vac |
| Input Frequency Range | 47-63 Hz |
| Input Current | 2.5 A typ. @ 115 Vac, 1.3 A typ. @ 230 Vac |
| Efficiency at 100% Load | 90.5% typ. @ 230 Vac |
| Max Inrush Current | 40 A typ. @ 230 Vac |
| Mechanical | |
| Case Cover / Chassis | SGCC / Aluminum |
| Indicator | Green LED (DC OK) |
| Cooling System | Convection |
| Input Terminal | 3 Pins (Rated 300 V / 30 A) |
| Output Terminal | 4 Pins (Rated 300 V / 20 A) |
| Noise – Sound Pressure Level (SPL) | < 25 dBA |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Unit Weight | 0.62 kg (1.37 lb) |
| Dimensions (H x W x D) | 123.6 x 40 x 116.8 mm 4.87” x 1.57” x 4.60” |
| Environment | |
| Vibration (Operating) | IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz @ 19.6 m/s² (2 G peak); 10 min per cycle, 60 min for X direction |
| Shock Test (Operating) | IEC 60068-2-27, Half Sine Wave: 10 G for duration of 11 ms; 1 time in X axis |
| Operating Temperature | -40°C to +70°C |
| Storage Temperature | -40°C to +85°C |
| Power De-rating | > 40°C de-rate power by 1.67 % / °C @ 115 Vac > 50°C de-rate power by 2.5 % / °C @ 230 Vac Input voltage < 100 Vac de-rate power by 1 % / Vac |
| Operating Humidity | 20 to 95% RH (Non-Condensing) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction, 9 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09 G); 20 min per axis for all X, Y, Z direction |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Pollution Degree | 2 |
| Over Voltage Category | II (Compliance to EN 62477-1 OVC III with 2000 meters altitude) |
| Protections | |
| Overvoltage | < 64.8 V, SELV Output, Latch Mode |
| Overload / Overcurrent | 105 - 150% of rated load current, Auto-recovery Continuous current limit Mode (Vo > 80%) |
| Over Temperature | Latch Mode |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Protection Against Shock | Class I with PE (Primary Earth) connection |